Pressure Tank Sizing Calculator

Looking for thermal expansion tank sizing instead? Expansion Tank Sizing →

Pump Control Type

To avoid short-cycling.

Affects the gauge-to-absolute pressure conversion used internally.

Formula Reference

Drawdown Volume

Vd=Q×tminV_d = Q \times t_{min}

Required Tank Volume

Vt=Vd1−Plow/PhighV_t = \dfrac{V_d}{1 - P_{low}/P_{high}}

Q = drawdown flow rate, t_min = minimum run/sleep time, V_d = drawdown volume, P_low/ P_high = absolute low/high pressure, V_t = required tank volume.

The required-volume formula has the same shape as the V_t = V_e / (1 - P_fill/P_max) formula on the thermal expansion tank page — same physics (a fixed volume that must be absorbed within a pressure charge), different source of that volume.