Expansion Tank Sizing Calculator

Looking for hydropneumatic pressure tank sizing instead? Pressure Tank Sizing →

System Type

A rough estimate of piping's contribution to total system volume, not a precise take-off.

Optional, defaults to 1.0. Accounts for fittings/terminal units not captured by the piping estimate above.

Reference data currently covers water from 0-100 °C.

Reference data currently covers water from 0-100 °C.

These come from the specific water heater's relief valve / PRV setting, or the hydronic system's design pressure — not a code table.

Affects the gauge-to-absolute pressure conversion used internally.

Formula Reference

Expansion Volume

Ve=Vsystem(ρcoldρhot−1)V_e = V_{system} \left(\dfrac{\rho_{cold}}{\rho_{hot}} - 1\right)

Required Tank Volume

Vt=Ve1−Pfill/PmaxV_t = \dfrac{V_e}{1 - P_{fill}/P_{max}}

V_system = derived system volume, ρ_cold/ρ_hot = water density at cold/hot temperature, V_e = expansion volume, P_fill/P_max = absolute fill/max operating pressure, V_t = required tank volume.