Engineering Calculators

Natural Smoke and Heat Venting (NFPA 204)

Vent and inlet areas for curtained areas by the hand calculations of NFPA 204 (2021), Section 9.2, with the dimension and spacing rules of Chapters 5 to 7. Add as many curtained areas and design fires as the project needs.

Chapters 4 to 10 of the standard are for nonsprinklered single-story buildings (1.1.1). Venting in a sprinklered building needs an engineering analysis the authority having jurisdiction accepts (11.1). The method is not valid for a fire above 12,000 zs5/2 kW (1.3.5) or while the smoke layer is above 600 °C (1.3.4); the results flag both.

1. Project and conditions

For your own reference. It is not part of the calculation.

Design ambient air temperature To (Equation 9.2.4.3).

Assumptions of the method

Leave blank to use the value in the placeholder. Change one only with a reason you can put in the report.

Q = c (t/tg)². Clauses 8.3.1 and 8.3.5 print 1055; Annex A.8.3.2 and the Annex D sample problem use 1000.

Fraction of the convected energy in the smoke layer (9.2.4.4). 0.5 unless the AHJ accepts an analysis for another value.

Ideal-gas value at the ambient temperature when blank.

Your entries are kept in this browser only, so you can reload without losing them. They are never sent anywhere except to run the calculation.