The rules and tables here follow the 2024 edition of NFPA 14 as printed (Chapters 5, 8, 10 and 11). The pressure of the other standpipes, the static pressure at the hose connections and the published friction loss of the hose valve are not covered, so confirm them separately, and check the class and type of system with the authority having jurisdiction.
Class of system Class I: 2.5 in. hose connections for the fire department Class II: 1.5 in. hose stations for trained personnel Class III: both 1.5 in. hose stations and 2.5 in. connections
Class I 2.5 in. hose connections to supply water for use by fire departments and by those trained in handling heavy fire streams (8.2.1). Flow: 500 gpm at the most remote standpipe (250 gpm at each of two connections), plus 250 gpm for each additional standpipe.Class II 1.5 in. hose stations to supply water for use by trained personnel, or a hose connection for the fire department during initial response (8.2.2.1). Each connection for trained personnel is equipped with no more than 100 ft of listed, lined 1.5 in. hose ready for use (7.6.2.1). Flow: 100 gpm at the most remote hose connection, and no extra flow where there is more than one connection.Class III Both: 1.5 in. hose stations for use by trained personnel and 2.5 in. hose connections for the fire department and those trained in handling heavy streams (8.2.3). Flow: Same flow as Class I.The authority having jurisdiction decides the class and type of system a building needs (4.1.1), so ask it if you are unsure. For Class III in a building sprinklered throughout, the 1.5 in. hose stations may be left out, subject to the AHJ, if each 2.5 in. connection has a 2.5 x 1.5 in. reducer and a cap on a chain (8.2.3.2). Clause numbers are from the 2024 edition.
Sprinkler protection No sprinklers Sprinklered throughout (NFPA 13) Partly sprinklered
Decides how a sprinkler demand combines with the standpipe demand.