Conduit Fill Calculator

A short piece between boxes, cabinets or similar enclosures may be filled to 60 % of its area (PEC Chapter 10, note 4), whatever the number of conductors.

Fill Reference

Allowed Fill Percentage

Conductors in ConduitAllowed Fill
153%
231%
3 or more40%
Nipple of not more than 600 mm, any number60%

Source: Philippine Electrical Code (PEC) Part 1, 2017 Edition — Table 10.1.1.1 — Percent of Cross Section of Conduit and Tubing for Conductors.

Table 10.1.1.4 — Dimensions and Percent Area of Conduit and Tubing